I/O Pins for PSS/E Data

Excel Template

The I/O pins for PSS/E models are defined in the Excel Template mentionned in https://opal-rt.atlassian.net/wiki/spaces/EUD/pages/edit-v2/23199830#Prepare-the-I%2FO-Pins-File.

The Excel file must have the following pages:

  • General: basic information of the power system, see https://opal-rt.atlassian.net/wiki/spaces/EUD/pages/23216542/Introduction+to+Excel+Template#General

  • Pins: used to define the required incoming and outgoing ports, see  Introduction to Excel Template | IntroductiontoExcelTemplate Pins

The following pages can be used and are optional:

Pins identifiers in PSS/E and Excel File

During a PSS/E import, the names of the components will change compared to their PSS/E names. These modified names are those required to define the pins.

The convention for creating the PSS/E names used for pins IDs is based on a combination of prefixes, bus names, and identifiers found in the PSS/E RAW and DYR files. The identifiers in PSS/E RAW files are one or two-character uppercase non-blank alphanumeric. The table below lists this convention.

Alternatively, you can access the modified names by running the simulation once without any pins to get the list of components from the *_solver.opal file.

You can then use those names to access the component and its pins.

The I/O pins for PSS/E input files only support positive sequence components listed in Native Library.

PSS/E Format and Example

OPAL Format Convention

Notes

PSS/E Format and Example

OPAL Format Convention

Notes

BUS
30

bus_
e.g.: bus_30



LOAD
Load with ID 1 connected to bus 10

load_Z_ , load_I_ , or load_P_
e.g.: load_Z_10_1

Z, I , P reflect constant impedance, current, and power

Fixed Shunt and Switch Shunt
Shunt with ID 1 connected to bus 10

fSH_ or swSH_
e.g.: fSH_10_1



GENERATOR
Generator with ID G1 connected to bus 39

gen_
e.g.: gen_39_G1

Type and dynamic data are read from *.dyr file

BRANCH (line)
Line with ID 1 between bus 9 and 39

line_b1_to_b2
e.g.: line_9_to_39_1



2-Winding TRANSFORMER
Transformer with ID T1 between bus 2 and 30

xf_b1_to_b2
e.g.: xf_2_to_30_T1



3-Winding TRANSFORMER
Transformer with ID T1 between buses 100, 101, and 102

xf_b1_b2_b3
e.g.: xf_100_101_102_T1



Excitation system
Exciter at bus 37 connected to machine with ID G1

ex_
e.g.: ex_37_G1

Type and dynamic data are read from *.dyr file

Power system stabilizer
PSS at bus 38 connected to machine with ID 2

pss_
e.g.: pss_38_2

Turbine-governor
TG at bus 37 connected to machine with ID 1

tg_
e.g.: tg_37_1