OP4510 V2 Certification and Standards
This product meets the essential requirements of applicable European Directives as follows:
The essential requirements of the directive 2014/30/EU are covered by the following harmonized standards:
EN61326-1 (2013) – Electrical equipment for measurement, control and laboratory use. The immunity test requirements used for this Product qualification are for the equipment intended to be used in an industrial electromagnetic environment.
Certifying body | Standard number | Standard Name | Specifications | Minimum performance requirement criteria |
---|---|---|---|---|
FCC part 15 (2018), subpart B | Conducted Emissions | Class A 150kHz-30MHz | ||
FCC part 15 (2018), subpart B | Radiated Emissions | Class A 30MHz-18GHz | ||
ICES-003 (2016) | Radiated Emissions | Class B 30MHz-18GHz | ||
ICES-003 (2016) | Conducted Emissions | Class A 150kHz-30MHz | ||
IEC61000-4-2 (2008) | Electrostatic Discharge Immunity | Contact: ±4kV Air: ±8kV | B | |
IEC61000-4-3 (2006) A1 (2007) A2 (2010) | Radiated Electromagnetic Field Immunity | 80MHz-1000MHz: 10V/m | ||
IEC61000-4-4 (2012) | Electrical Fast Transient Immunity | Power: ±2kV / 5kHz | B | |
IEC61000-4-5 (2014) | Surge Immunity | Power: ±2kV L-PE / ±1kV L-L | B | |
IEC61000-4-6 (2013) | Immunity to Conducted Disturbances, Induced by Radio-Frequency Fields | Power: 3V | A | |
IEC61000-4-8 (2009) | Power Frequency Magnetic Field Immunity | Continuous Field: 30A/m / 50Hz & 60Hz | A | |
IEC61000-4-11 (2004) | Voltage Dips, Short Interruptions and Voltage Variation Immunity on AC Input | Voltage dips: |
| |
CISPR11 (2015) A1 (2016) | Conducted Emissions | Group 1 - class A 150kHz-30MHz | ||
CISPR11 (2015) A1 (2016) | Radiated Emissions | Group 1 - Class A 30MHz-1GHz | ||
IEC61010-1:2010 (Third edition) | Single fault condition Protective Conductor Abnormal Cooling Abnormal Input Durability Of Markings Applied Force Permissible Limits For Accessible Parts Impedance Of Protective Bonding Test Dielectric Voltage Withstand Humidity Conditioning Capacitor Discharge Stability 10 Deg Static Rigidity Impact Drop (Non-Hand Held Equipment) Temperature | 4.4.1 4.4.2.3 4.4.2.10 5.1.3 5.3 6.2.2 6.3 6.5.2.4 6.8 6.8.2 6.10.3 7.4a 8.2.1 8.2.2 8.3.1 10.1-10.4 |