Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Distribution Grid Example

The following figure shows a typical configuration of a distribution grid. Such a model is used to study the impact of various load profiles and control strategies.

This distribution system (F1a) with an on-load tap changer (OLTC) transformer at the feeder point, 120 3-phase time-variable loads (TVL), 3-phase fault and more than 650 equivalent EMTP nodes is simulated in real-time with the SSN solver.

15 SSN nodes were used in the separation of the F1a network (The SSN nodes are the 5 red dots in the image).

F1a distribution grid

Real-Time Performance

The F1a model with OLTC and one 3-phase fault can be simulated in real-time at a time-step of 70 µs on an Intel-Xeon Processor-E5-2687W (Xeon V3), using only 4 cores out of the 20 available, without any delays or stublines. 

See References for more detail on this model. This performance is currently out of reach for other real-time platforms such as Hypersim or RTDS because there are no long transmission lines in distribution systems

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323