Block

Mask

Description

The National InstrumentsNI6703 and NI6704 cards feature 16 voltage outputs and 8 digital I/O lines. The NI6704 card also features 16 current outputs. This block monitors the voltage or current analog output channels.

Parameters

Bus TypeSelect the bus type (PCI or PXI) of the target node in this list.
Card TypeSelect the card model in this list.
PCI indexEnter the PCI index (see definition)of the card on the PCI (or PXI) bus.
Output Type

[NI-6704only] Select the type of outputs desired. The choices are voltage(output in volts) or current (output in amps). To output data to both voltage and current channels, use one block for voltage channels and another one for current channels.

Channel ListEnter the vector of channel numbers to be monitored by this block. The channel numbers, in the range [0-15], can be entered in any order and must appear only once in the list.
Synchronizesee definition.


Inputs

At each calculation step of the model, the block writes to the output channels the data provided by the model through the inports of the block. The input values are assumed to be in volts or in amps, depending on the output type selected in the mask.



Note: The output ranges are [-10V,+10V] or [0,20mA].



Three sets of input values must be specified :

reset

Values that will be written to the analog out channels when the reset button is hit.

pause

Values that will be written to the analog out channels when the model is in pause mode, that is at initialization or when the pause button is hit.

run

Values that will be written to the analog out channels at each time step.



Note: To ensure that the pause and reset values be properly written out, it is recommended to set these values in the model subsystem that contains the Op NI670xAnalog Out block, and not to provide them from the console subsystem.


Outputs

This block has no outputs.

Characteristics and Limitations

Connector Pin Assignments

The following table gives the description of the signals related to the analog output channels and is followed by the connector pin assignments of the 68-pin I/O connector.

Signal Name Signal Description 
VCH0..15 Voltage analog output channels. 
ICH0..15 [NI6704 only] Current analog output channels. 
AGND0..31, AGND Analog output ground pins.

68-pin I/O

Pin Description Pin Description 
34VCH0 68AGND0/AGND16 
33AGND1/AGND17 67ICH16 
32ICH17 66VCH1 
31VCH2 65AGND2/AGND18 
30AGND3/AGND19 64ICH18 
29ICH19 63VCH3 
28VCH4 62AGND4/AGND20 
27AGND5/AGND21 61ICH20 
26ICH21 60VCH5 
25VCH6 59AGND6/AGND22 
24AGND7/AGND23 58ICH22 
23ICH23 57VCH7 
22VCH8 56AGND 
21ICH24 55AGND8/AGND24 
20AGND9/AGND25 54VCH9 
19AGND 53ICH25 
18AGND10/AGND26 52VCH10 
17VCH11 51ICH26 
16ICH27 50AGND11/AGND27 
15VCH12 49AGND12/AGND28 
14AGND13/AGND29 48ICH28 
13ICH29 47VCH13 
12VCH14 46AGND14/AGND30 
11AGND15/AGND31 45ICH30 
10ICH31 44VCH15 
9DIO743AGND 
8DIO642DGND
7DIO541DGND
6DIO440RFU
5DIO339DGND
4DIO238RFU
3DIO137DGND
2DIO036DGND
1+5V35DGND
Direct FeedthroughNo
Discrete sample timeNo
XHP supportYes
Work offlineNo

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323