Verify that the mains supply is disconnected and that no external energy source is connected to the OP1460 or OP1480 terminals before opening the cabinet doors or the PDU when troubleshooting. Failure to do so could expose the user to risks of electric shocks. Refer to OP1400 Series Important Safety Information - Manipulation of the test setup for more information.
Verify that the power knob on the DC power supply is set to the ON (I) position
Verify that the 3-phase mains input disconnect switch (at the back of the test bench, on the PDU, and/or building disconnect switch) is turned on
Verify that the circuit breaker on the 3 phase mains input (inside the PDU or building breaker) is activated and has not tripped, refer to problem Overcurrent protection on 3 phase mains input keeps tripping when working in the medium to high power range on the test bench if this problem keeps reappearing
Verify that the Emergency Stop on OP1490 is deactivated (+24V_E-STOP LED must be lit), rotate the Emergency Stop button clockwise if not the case, refer to problem OP1490: +24V_E-STOP light does not turn on when releasing the EMERGENCY STOP button if necessary
Verify that the DC OK LED light on the MDR-60-24 Power Supply (photo below) is ON inside the PDU. If not, make sure all 120V connections on the Power Bar(s) are well done (no loose)
Verify that the signal harness on the rear panels of the OP1490 (E-STOP connector) and on the rear panel of the OP1460/1480 (P1 connector) are correctly plugged in
Verify that the Start/Stop button is lit on the OP1490, press Start if not the case, refer to problem OP1490: Start/Stop button not working if necessary
Overcurrent protection on 3 phase mains input keeps tripping when working in the medium to high power range on the test bench
For test bench models with more than one DC power supply, verify that the 3 phase connections are interleaved from one power supply to another to ensure balanced three-phase current, as documented in OP14xx Installation - Reassembling the rack
OP8110 Amplifier ends up in an undervoltage/overvoltage fault when power starts being consumed/produced
OP8110 Amplifier seems to produce an output voltage but it does not appear on OP1460's DER outputs
Verify that the DER channel is turned ON (the light between the Start/Stop button must be lit), refer to problem OP1460: DER outputs cannot be turned on if necessary
OP8110 Amplifier seems to produce an output voltage but it does not appear on OP1480's outputs
Verify that the proper channel is turned ON (the light between the Start/Stop button must be lit), refer to problem OP1480: outputs cannot be turned on if necessary
OP8110 Amplifier does not produce an output voltage
Verify that the SFP cable is correctly connected between the amplifier (right SFP port) and the simulator
Verify that the SFP communication link has been correctly configured in RT-LAB and that the model is running (measurements coming from the amplifier should have a little noise)
Verify that the OP8110 amplifier unit is turned ON (the light inside the power-on button on the front panel is green), refer to problem OP8110 Amplifier does not turn ON if necessary
OP8110 Amplifier: unable to enable the DC link through RT-Lab (DC precharge never starts)
Verify that the SFP cable is correctly connected between the amplifier (right SFP port) and the simulator
Verify that the SFP communication link has been correctly configured in RT-LAB and that the model is running (measurements coming from the amplifier should have a little noise)
Verify that the OP8110 amplifier unit is turned ON (light inside power-on button on the front panel is green), refer to problem OP8110 Amplifier does not turn ON if necessary
Power down the DC supply and wait for 5 minutes before reenabling the precharge sequence, refer to OP8110 Power Stage (DC Precharge section).
OP8110 Amplifier: unable to enable an amplifier output through RT-Lab
Verify that the SFP cable is correctly connected between the amplifier (right SFP port) and the simulator
Verify that the SFP communication link has been correctly configured in RT-LAB and that the model is running (measurements coming from the amplifier should have a little noise)
Try clicking on the DISABLE button before retrying the ENABLE button (GUI synchronization issue that arises when trying to enable outputs too rapidly).
OP8110 Amplifier does not turn ON
Verify that the auxiliary supply harnesses (one for OP8110-3, two for OP8110-6) are correctly plugged-in on the OP8110's 12V AUX connectors on the rear panel
Verify that the signal harness on the rear panels of the OP1490 (PS_AUX_CONNECTOR) is correctly plugged in
Verify that all the +12V PS_AUX LEDs are lit on the OP1490, refer to problem OP1490: one or more of the +12V PS_AUX lights are not lit if necesary
OP1470's power meters not functional
Verify that all power bars inside the test bench are plugged in and turned ON (indicator light should be lit on power bars)
Verify that the supply inlet is plugged into the rear panel of the OP1470.
Verify that the power switch is turned ON (I) on the OP1470's rear panel
OP1470: one or more power meter does not show correct voltages or currents
Verify that all the signal connectors (V_uGRID, I_uGRID, V_DERx and I_DERx) have their harnesses plugged-in on OP1470's rear panel and that they are correctly mapped (refer to labels on signal harnesses)
Verify that all the signal connectors (V_uGRID, I_uGRID, V_DERx and I_DERx) have their harnesses plugged-in on OP1460's rear panel and that they are correctly mapped (refer to labels on signal harnesses)
OP1460 is not supplied (24V ON light is not lit)
Verify that the Emergency Stop on OP1490 is deactivated (+24V_E-STOP LED must be lit), rotate the Emergency Stop button clockwise if not the case, refer to problem OP1490: +24V_E-STOP light does not turn on when releasing the EMERGENCY STOP button if necessary
Verify that the signal harness on the rear panels of the OP1490 (E-STOP connector) and on the rear panel of the OP1460 (P1 connector) are correctly plugged in
Verify that a DB37 harness is connected between the OP1460's C1 connector (rear panel) and the appropriate digital output connector of the simulator
Verify that the digital output module of the simulator is correctly configured (a loopback test can be done with the DB37 harness looping back to a digital input module)
OP1480 is not supplied (24V ON light is not lit)
Verify that the Emergency Stop on OP1490 is deactivated (+24V_E-STOP LED must be lit), rotate the Emergency Stop button clockwise if not the case, refer to problem OP1490: +24V_E-STOP light does not turn on when releasing the EMERGENCY STOP button if necessary
Verify that the signal harness on the rear panels of the OP1490 (E-STOP connector) and on the rear panel of the OP1480 (P1 connector) are correctly plugged in
Verify that the DC OK LED light on the MDR-60-24 Power Supply (photo below) is ON inside the PDU.
OP1480: outputs cannot be turned ON (the light between the Start/Stop button does not turn ON)
Verify that the 24V ON light is lit on the OP1480's front panel, refer to problem OP1460 is not supplied if necessary
OP1490: one or more of the +12V PS_AUX lights are not lit
Verify that all power bars inside the test bench are plugged in (Double Check for any loose connection) and turned ON (indicator light should be lit on power bars)
Verify that the supply inlet is plugged into the rear panel of the OP1490
Verify that the power switch is turned ON (I) on the OP1490's rear panel
Verify that the fuses on the OP1490's front panel are intact, replace if necessary.
OP1490: Start/Stop button not working (light does not turn on or does not maintain itself on when pressing Start)
Verify that the signal harness on the rear panels of the OP1490 (START-STOP connector) is correctly plugged in
Verify that all power bars inside the test bench are plugged in (double-check for any loose connection) and turned ON (indicator light should be lit on power bars).
Verify that the supply inlet is plugged into the rear panel of the OP1490
Verify that the power switch is turned ON (I) on the OP1490's rear panel
Verify that the DC OK LED light on the MDR-60-24 Power Supply (photo below) is ON inside the PDU.
OP1490: +24V_E-STOP light does not turn on when releasing the EMERGENCY STOP button
Verify that all power bars inside the test bench are plugged in (double-check for any loose connection) and turned ON (indicator light should be lit on power bars).
Verify that the supply inlet is plugged on the rear panel of the OP1490
Verify that the power switch is turned ON (I) on the OP1490's rear panel
Verify that the right-most fuse on the OP1490's front panel is intact, replace if necessary
Verify that the DC OK LED light on theMDR-60-24 Power Supply (photo below) is ON inside the PDU.
Need additional support?
For any issue or technical requests not covered in this manual, refer to our online Knowledge Base.