Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Frequency Protection


image-20240606-212731.png

This block is used to detect abnormal conditions in the grid’s frequency. For this purpose, a set of regions can be specified by the user as per [1]. A maximum of 8 different regions can be specified for over and under-frequency events, respectively. Also, this block detects when the average Rate of Change of Frequency (ROCOF) is above a specific threshold. 

Mask and Parameters

image-20240122-190127.png

 

Name

Description

Unit

Name

Description

Unit

Nominal Frequency

Nominal operating frequency

Hz

 

 

 

 

 

Name

Description

Unit

Number of Over-Frequency Points

Number of over-frequency regions delimited by a set of frequency points

-

Frequency Points [Point1,…, Point 8]

Limit frequency values before reaching the respective over-frequency trip region

Hz

Time Points [Point1,…, Point 8]

Amount of time that the converter must operate in a frequency region before tripping

s

 

 

 

 

Name

Description

Unit

Number of Under-Frequency Points

Number of under-frequency regions delimited by a set of frequency points

-

Frequency Points [Point1,…, Point 8]

Limit frequency values before reaching the respective under-frequency trip region

Hz

Time Points [Point1,…, Point 8]

Amount of time that the converter must operate in a frequency region before tripping

s

 

 

 

 

Name

Description

Unit

ROCOF Threshold

Maximum allowed Rate of Change of Frequency (ROCOF) value before activating trip signal

Hz/s

Averaging Time Window 

The time constant for the first-order average filter block for the Rate of Change of Frequency (ROCOF) estimation.

s

 

Inputs, Outputs, and Signals Available for Monitoring

Inputs

Name

Description

Unit

Name

Description

Unit

Frequency

Grid frequency

Hz

 

Outputs

Name

Description

Unit

Name

Description

Unit

UOF

Trip signal for under or over-frequency events

-

ROCOF

Trip signal for Rate of Change of Frequency (ROCOF) events

-

 

References

[1]

IEEE, "IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces," IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003), no. doi: 10.1109/IEEESTD.2018.8332112, pp. 1-138, 2018.

[2]

IEEE, "IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces," IEEE Std 1547.1-2020, pp. 1-282, 2020.

 

Intellectual Property Disclaimer

Natural Resources Canada owns all intellectual property rights in the Smart Inverter Modelling Toolbox software and related products.

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323