Documentation Home Page ◇ MMC Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
Full-Bridge Topology Maximum Cell Number Test
This test is designed to test the maximum number of cells that can be operated per arm. To achieve the test purpose, we can observe the value variation of the total Vcap in Total Vcap display block after fixing all cell’s Vcap to a fixed value (for example: 1).
- System initialization.
- To test the total number of cells per arm, the number of cells per arm in MMC Parameter block should be changed to the maximum value which is intended to be tested (For example: 500).
- In MMC parameter block, change the set Vcap fix value to 1. Pay attention to the Total Vcap display block in the console.
If the number displayed in the Total Vcap display block equals to the number of cells per arm set in the MMC parameter block, it shows that all set cells per arm can be operated. As shown in Figure 32.
The maximum number of cells can be operated depends on the license.
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter