TGOV1
Description
The block diagram of Governor/Turbine system model. This model present a governor action, reheater time constant, and the ratio of high-pressure turbine.
Mask and Parameters
Exciter Parameters
Expanding the "Block diagram" displays the block diagram in the parameters window.
Name | Description | Unit |
Dt | Turbine damping coefficient | pu |
R | Permanent droop | pu/pu |
T1 | Steam bowl time constant 1 | s |
T2 | Time constant 2 | s |
T3 | Time constant 3 | s |
Vmax | Maximum valve position | pu |
Vmin | Minimum valve position | pu |
W0* | Speed reference | pu |
*The speed reference can be set manually, by entering a numerical value in the W0 field of the parameters window. It can also be set automatically based on load flow calculations, by entering a referenced synchronous machine variable.
Machine variables can be found in the machine netlist. For instance, if the name of the synchronous machine on which the governor/turbine is connected is “SM1”, then the speed reference should be inserted as “=SM1.wo” if a thermal machine or a hydraulic machine is used, and as "=SM1.Wm_Init" if a pu standard or pu fundamental machine is used.
The HYPERSIM simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
Inputs and Outputs and Additional Signals Available for Monitoring
Inputs
Name | Description | Unit |
SpeedFreq | Speed or Frequency input | pu |
Pref | Reference electrical power | pu |
Outputs
Name | Description | Type |
Tmec | Mechanical Torque Output | pu |