TGOV2


Description

The block diagram for the governor/turbine system model presents a governor action, reheater time constant, and the ration of high-pressure turbine, with fast valving action.

Mask and Parameters

AVR parameters

TGOV2 mask parameters

Expanding the "Block diagram for TGOV2" displays the block diagram in the parameters window.

Block diagram TGOV2



Name

Description

Unit

R

Permanent droop

pu/pu

Dt

Turbine damping coefficient

pu

T1

Steam bowl time constant 1

s

T3

Time constant 3

s

K

Governor gain

pu

TT

Valve time constant

s

Vmax

Maximum valve position

pu

Vmin

Minimum valve position

pu

Fast valving parameters

[TI TA TB TC] *

s

* The T1 parameter should remain at zero, to have a reference in the x-axes.

The speed reference can be set manually, by entering a numerical value in the W0 field of the parameters window. It can also be set automatically based on load flow calculations, by entering a referenced synchronous machine variable. Machine variables can be found in the machine netlist. For instance, if the name of the synchronous machine on which the governor/turbine is connected is “SM1”, then the speed reference should be inserted as “=SM1.wo” if a thermal machine or a hydraulic machine is used, and as "=SM1.Wm_Init" if a pu standard or pu fundamental machine is used.

The HYPERSIM simulation option “Set Initial Conditions” must be checked for the automatic initialization to work properly.

Inputs and Outputs and Additional Signals Available for Monitoring

Inputs

NameDescription

Unit

SpeedFreq

Speed or frequency input

pu

Pref

Reference electrical power

pu

Outputs

NameDescription

Type 

Tmech

mechanical torque output

pu