Transformer Data Tab | Parameters GUI & Toolbox Icons
Parameters Tab
Toolbox Icons
Compute | Compute the transformer data, the results are shown in the Log Report. |
---|---|
Revert | Revert to default transformer data |
Open | Load your transformer model *.htd (hypertransfo data file) |
Save | Saves your transformer data in a new *.htd (hypertransfo data file) file that contains the information of the model |
Description And Parameters
Frequency | Specify the frequency in hertz (Hz) to be used |
---|---|
Nominal power | Specify the nominal power of the transformer in volt-amperes (VA) |
Comments | Use this window to type any comments or details that you wish to save with the transformer parameters |
Units | In the pull-down menu, select “SI” of “PU” |
Zero sequence data available | Checkbox if the zero sequence data is available
|
Zero sequence X12 measured with winding 3 delta connected | Checkbox if the available zero-sequence short circuit tests measurement of winding 3 is connected in Delta. |
Nominal voltages | Specify the nominal voltages phase-to-phase of the winding to be used in the model in volts RMS |
Winding resistances | Specify the winding resistances |
Excitation Data
Positive-sequence | Zero-sequence | |
---|---|---|
no-load excitation current | Specify the no-load excitation current in percent (%) of nominal current when positive-sequence nominal voltage is applied at any group of winding terminals. | Specify the no-load excitation current in percent (%) of nominal current when zero-sequence nominal voltage is applied at any group of winding terminals. |
no-load Losses | Specify the no-load losses. The core losses and the winding losses at no-load in watts (W), when positive-sequence nominal voltage is applied at any group of winding terminals. | Specify the no-load losses in watt. The core losses and the winding losses at no-load in watts (W), when zero-sequence nominal voltage is applied at any group of winding terminals. |
short-circuit reactance | Specify the short-circuit reactance (Xij) X12, X23 and X13, when the winding i and j is shortcircuited. | Specify the short-circuit reactance (Xij) X12, X23 and X13, when the winding i and j is shortcircuited. If the Zero sequence X12 measured with winding 3 delta connected is not checked, X12 represents the short-circuit reactance when winding 3 is not connected in Delta. |
Load Parameters
The Load Parameters button updates the transformer parameters in the General Tab of the parameter form. It can be verified by comparing the result obtained in the Log tab of the parameter form.