Documentation Home Page ◇ OPAL-RT Schematic Editor Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
Surge Arrester IV parameters file
How to specify IV parameters file in the Schematic Editor ?
The Surge Arrester block has a "Current voltage characteristic" parameter which is a dropdown. When the "Current-voltage table" is selected, you can specify a file which should contain current voltage characteristics in the "Current voltage lookup table" field.
This file has to be in a specific format which is described below.
What is the format of the IV parameters file ?
The current voltage parameters are described in a JSON format. The following parameters must appear in the file.
Paremeter (JSON key) | Value type | Unit | Description | Example |
---|---|---|---|---|
currentBreakpoints | double[] | A | Current breakpoints of the Surge Arrester | "currentBreakpoints":[ 0.0, 1.0e-3, 3.0e-3, 1.0e-2, 1.0e-1, 10.0, 200.0, 600.0 ], |
voltageValues | double[] | V | Voltage values for each current breakpoint of the Surge Arrester | "voltageValues": [ 0.0, 426.4e3, 450.18e3, 455.92e3, 467.4e3, 501.84e3, 519.88e3, 527.26e3 ] |
All the examples above concatenated would give in a valid JSON format:
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323