Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

WESGOV


Description

This model is the Westinghouse digital governor for gas turbines. The WESGOV component was developed in line with the reference [1].

Mask and Parameters

WEHGOV Parameters

Expanding the "WESGOV block diagram" displays the block diagram in the parameters window.



Name

Description

Unit

Variable = {Possible Values}

delTC

The sample period for the speed measurement

s

-

delTP

The sample period for the electrical power measurement

s

-

Droop

Power droop

pu

-

KP

Controller proportional gain

-

-

TI

Controller integral time constant

s

-

T1

Actuator time constant

s

-

T2

Actuator time constant

s

-

Alim

Maximum change between samples

pu

-

TPE

Electrical power transducer time constant

s

-

Initial Values Tab

Name

Description

Unit

Variable = {Possible Values}

Pm0

Initial mechanical power output

pu

--

w0

Speed reference

pu

--


The speed reference can be set manually, by entering a numerical value. It can also be set automatically based on load flow calculations, by entering a referenced synchronous machine variable. Machine variables can be found in the machine netlist. For instance, if the name of the synchronous machine on which the governor/turbine is connected is “SM1”, then the speed reference should be inserted as “=SM1.wo” if a thermal machine or a hydraulic machine is used, and as "=SM1.Wm_Init" if a pu standard or pu fundamental machine is used.

The same goes for the initial power output of the machine Pm0. Pm0 shall be set as =SM1.Peo/SM1.BaseMVA, if a thermal machine or a hydraulic machine is used, and as "=SM1.lfP/1e6/SM1.sBase" if a pu standard or a pu fundamental machine is used, where Peo and IfP are the initial power outputs of the machines, respectively.

The HYPERSIM simulation option “Set Initial Conditions” must be checked for the automatic initialization to work properly.

Inputs and Outputs and Additional Signals Available for Monitoring

Inputs

I/O name

Description

Unit

w

Machine actual speed

pu

Ref

External control reference

pu

Pe

Measured electrical power

pu


Outputs

I/O name

Description

Unit

Pm

Mechanical power output

Output 

References

[1] PSS®E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323