Load Management

image-20240916-093050.png

The Load Management Control block is responsible for regulating the flow of the load (active power) through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the active power settings. This block is part of the microgrid library from the OP1420, and should be used along with the other blocks.

image-20240916-095147.png

Mask and Parameters

This block is part of the microgrid library from the OP1420, and should be used along with the other blocks.

Name

Unit

Description

Name

Unit

Description

Diesel minimum power

pu

Minimum values for Diesel generation

Diesel maximum power

pu

Maximum values for Diesel generation

BESS maximum power

pu

Maximum values available for BESS

Load shedding maximum reduction

pu

Maximum values of Load shedding reduction

 

Inputs, Outputs and Signal Available for monitoring

Inputs

Name

Unit

Description

Name

Unit

Description

Pref RER

pu

Combined reference powers for all Renewable Energy Resources (RERs) (WT+PV)

P ref Total Load

pu

Combined reference powers for all loads (DR, Sheddable, Critical and PHIL)

P ref Shedable Load*

pu

User-defined power reference for sheddable load

P ref Excess Load

pu

Excess load within the Microgrid (greater than 0 means load must be reduced)

P ref Demand Response Load*

pu

Excess load within the Microgrid (greater than 0 means load must be reduced)

Islanded

-

Specifies whether the Microgrid is islanded/Grid connected (0 = Grid connected, 1 = islanded)

Dispatch mode

-

Internal mode of the real-power (dispatch) controller

 

Outputs

Name

Unit

Description

Name

Unit

Description

Total Load Reduction

pu

Total amount of load reduction used to adjust the BESS's power reference. 

P ref Demand Response Load

pu

Power reference sent to the demand response load

Demand Response Load Reduction

-

Status of the demand response load (0= load is not reduced, 1 = load is reduced)

P ref Sheddable Load

pu

Power reference sent to the sheddable load

Load Shedded

-

Status of the sheddable load (0 = load is not shedded, 1= load is shedded)

 