Documentation Home Page ◇ HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
Reactive Power Dispatch
The Reactive Power Control block is responsible for regulating the flow of reactive power through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the reactive power settings and maintain stability. This block is part of the microgrid library from the OP1420, and should be used along with the other blocks.
Mask and Parameters
The Reactive Power Controller block contains the following configuration mask:
Name | Unit | Description |
---|---|---|
reactiveLoad | pu | Reactive power load of the microgrid in per-unit. |
Inputs, Outputs and Signal Available for Monitoring
Inputs
Name | Unit | Description |
---|---|---|
QremainingDG | pu | Specify the remaining reactive power capacity of the Diesel Generator in per-unit |
statusDG | - | Status of the Diesel Generator (0 when disabled, 1 when enabled) |
QremainingBESS | pu | Specify the remaining reactive power capacity of the Battery Energy Storage System in per-unit |
statusBESS | - | Status of the Battery Energy Storage System (0 when disabled, 1 when enabled) |
QremainingWT | pu | Specify the remaining reactive power capacity of the Wind Turbine Generation System in per-unit |
statusWT | - | Status of the Wind Turbine Generation System (0 when disabled, 1 when enabled) |
QremainingPV | pu | Specify the remaining reactive power capacity of the Photovoltaic Generation System in per-unit |
statusPV | - | Status of the Photovoltaic Generation System (0 when disabled, 1 when enabled) |
QrequiredGrid | pu | Specify the requirement of reactive power from grid in per-unit |
PHIL_Qmeas | pu | Specify the reactive power measurement from the PHIL block in per-unit |
Outputs
Name | Unit | Description |
---|---|---|
QrefDG | pu | Reactive power reference of the Diesel Generator in per-unit |
QrefBESS | pu | Reactive power reference of the Battery Energy Storage System in per-unit |
QrefWT | pu | Reactive power reference of the Wind Turbine Generation System in per-unit |
QrefPV | pu | Reactive power reference of the Photovoltaic Generation System in per-unit |
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter