Islanding Management
The Islanded Control block is responsible for regulating the flow of the active and reactive power when the microgrid is disconnected from an external AC-grid, known as Islanded mode, by allowing the user to adjust the active and reactive power settings.
Mask and Parameters
Name | Unit | Description |
---|---|---|
Frequency | Hz | Expected grid frequency even during islanded mode. |
PCC dq-voltage threshold for Grid Connected transition | V | Maximum voltage threshold to close main grid break and leave islanded mode. |
PCC dq-current threshold for Isalnded transition | A | Minimum current threshold to open main grid break and enter islanded mode. |
Duration of below-threshold V/A for PCC switching | s | This is the duration where the condition must be met to enter or leave the islanded mode. To enter islanded mode, minimum current condition must be achieved for at least this duration. To leave islanded mode maximum voltage condition must be achieved for at least this duration. |
Microgrid phase error frequency compensation | Hz/rad | When the islanded microgrid and the grid are out of phase, this will modify the diesel generator frequency so both network can be synchronize before leaving the islanded mode. |
Inputs, Outputs and Signals Available for Monitoring
Inputs
Name | Unit | Description |
---|---|---|
P import Grid | pu | Active power P commanded by dispatch. |
Q import Grid | pu | Reactive power Q commanded by dispatch. |
P ref Grid | pu | Active power P commanded by user. |
Q ref Grid | pu | Reactive power Q commanded by user. |
P Grid | pu | Active power P measured through the Point of Common Coupling (PCC). |
Q Grid | pu | Reactive power Q measured through the Point of Common Coupling (PCC). |
wt Grid | radsec | wt of Infeed grid. |
Current Grid | A | Current measurement of Infeed grid. |
Voltage Grid | V | Voltage measurement of Infeed grid. |
Voltage Microgrid | V | Voltage measurement of microgrid. |
Islanded enable | - | User island command (should be set to 1 when the microgrid needs to be set in islanded mode). |
Angle Error Microgrid | - | Difference between microgrid and external grid angles. |
Outputs
Name | Unit | Description |
---|---|---|
P error Grid | pu | Error between commanded and measured active power P. |
Q error Grid | pu | Error between commanded and measured reactive power Q. |
PCC current zero enable | - | PCC current is low enough to open PCC. |
Current comparison result | - | PCC current status |
Current value | pu | PCC current |
PCC voltage zero enable | - | Voltage difference across PCC low enough to close. |
Voltage comparison result | - | PCC voltage status |
Voltage value | pu | PCC voltage |
Islanded | - | microgrid is islanded. |
w Ref DG | rad | w reference for Diesel generator to compensate microgrid angle error. |