BESS Management
This block contains the logic for summing all components of the BESS real power reference. These references are the main reference sent from the real power controller, the PCC real power error, the load reduction compensation, as well as a frequency compensation component calculated in this section which allows the BESS to aid the Diesel Generator in maintaining the Microgrid bus frequency during an islanded condition. This block also contains the logic for summing the reactive power reference components, which are simply the reference sent from the reactive power controller and the PCC reactive power error. This block is part of the microgrid library from the OP1420, and should be used along with the other blocks.
Mask and Parameters
The BESS Power Reference Compensation block contains the following configuration mask:
Name | Unit | Description |
---|---|---|
Global nominal power | W | The nominal power of the microgrid. Default value is 12e3. |
Nominal frequency | Hz | The nominal frequency of the microgrid. Default value is 50. |
Name | Unit | Description |
---|---|---|
BESS frequency compensation (kW per 0.1 Hz) | kW/Hz | Proportional control factor for BESS frequency compensation. Default value is 3. |
Name | Unit | Description |
---|---|---|
Time constant | s | Low pass filter time constant for power measurements, in seconds. The default value is 1. |
Bypass time | s | Wait time to bypass the filter. The default value is 5. |
Start of the dead zone | - | Specify dead zone lower limit. Set the value for Start of dead zone less than or equal to End of dead zone. The default value is -2e-3. |
End of the dead zone | - | Specify dead zone upper limit. Set the value for End of dead zone greater than or equal to Start of dead zone. The default value is 2e-3. |
Inputs, Outputs and Signal Available for Monitoring
Inputs
Name | Unit | Description |
---|---|---|
Frequency | Hz | The measured frequency of the microgrid |
Islanded | - | Specifies whether the Microgrid is islanded/Grid connected (0 = Grid connected, 1 = islanded) |
Total load reduction | pu | Total amount of load reduction used to adjust the BESS's power reference |
P ref BESS* | pu | Active power reference from dispatch controller |
Q ref BESS* | pu | Reactive power reference from dispatch controller |
P error Grid | pu | The active power difference between the active power transmit through the PCC and what the user demands |
Q error Grid | pu | The reactive power difference between the reactive power transmit through the PCC and what the user demands |
Outputs
Name | Unit | Description |
---|---|---|
P ref BESS | pu | Active power reference sent to the battery energy storage system |
Q ref BESS | pu | Rective power reference sent to the battery energy storage system |