Description

This frequency relay (81) includes three types of frequency elements, namely the overfrequency (81O), the under-frequency (81U), and the rate-of-change-of-frequency (ROCOF) (81R) elements. There are five levels of thresholds available with the 81O and 81U elements, whereas the 81R element features only one level.

Each level corresponds to a predefined frequency level and a tripping delay time. When the frequency or ROCOF monitored by the relay exceeds the settings, the relay operates. The model works for 50 Hz or 60 Hz system

Table of Contents

Model Overview



The frequency relay operates whenever the frequency or ROCOF measured from the input voltage signals using a zero-crossing detection logic exceeds the preset settings. 

A time delay is used to enable the relay to ride through momentary frequency fluctuations and thus prevent nuisance operation. The five-level characteristic of 81O and 81U are presented in Figures as shown below:

81O element characteristic
81O element characteristic

Characteristics of 81O

81U element characteristic
81U element characteristic

Characteristics of 81U



Mask and Parameters

General Parameters

The following parameters are tunable:

Name

Description

Unit

Variable = {Possible Values}

Name

Description

Unit

Variable = {Possible Values}

Frequency

The nominal frequency of the measured voltage signals.
Both 50 and 60 Hz are supported in the model.

Hz

Freq_param= {50, 60}

Freezing time

The freezing time of the 81 relay, when t < freezing time,
the 81 relay is not activated.

s

tunf_param = { [0.10, 60.00] }



Settings - Overfrequency

The following parameters are tunable:

Name

Description

Unit

Variable = {Possible Values}

Name

Description

Unit

Variable = {Possible Values}

Enable Overfrequency

Overfrequency element enable/disable

-

Enable_81O_param= {0, 1}

Level 1

Over-frequency level 1.

Hz

OLevel1_param={ [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 2

Over-frequency level 2.

Hz

OLevel2_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 3

Over-frequency level 3.

Hz

OLevel3_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 4

Over-frequency level 4.

Hz

OLevel4_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 5

Over-frequency level 5.

Hz

OLevel5_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Time 1

Time delay associated with Level 1.

s

OTime1_param= { [0, 600] }

Time 2

Time delay associated with Level 2.

s

OTime2_param= { [0, 600] }

Time 3

Time delay associated with Level 3.

s

OTime3_param= { [0, 600] }

Time 4

Time delay associated with Level 4.

s

OTime4_param= { [0, 600] }

Time 5

Time delay associated with Level 5.

s

OTime5_param= { [0, 600] }



Settings - Underfrequency

The following settings are tunable:

Name

Description

Unit

Variable = {Possible Values}

Name

Description

Unit

Variable = {Possible Values}

Enable  Underfrequency

Underfrequency element enable/disable

-

Enable_81U_param= {0, 1}

Level 1

Under-frequency level 1.

Hz

ULevel1_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 1

Under-frequency level 2.

Hz

ULevel2_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 1

Under-frequency level 3.

Hz

ULevel3_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 1

Under-frequency level 4.

Hz

ULevel4_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Level 1

Under-frequency level 5.

Hz

ULevel5_param= { [45, 55] } for 50 Hz Operation; { [55, 65] } for 60 Hz Operation.

Time 1

Time delay associated with Level 1.

s

UTime1_param= { [0, 600] }

Time 1

Time delay associated with Level 2.

s

UTime2_param= { [0, 600] }

Time 1

Time delay associated with Level 3.

s

UTime3_param= { [0, 600] }

Time 1

Time delay associated with Level 4.

s

UTime4_param= { [0, 600] }

Time 1

Time delay associated with Level 5.

s

UTime5_param= { [0, 600] }



Settings - ROCOF

The following settings are tunable:

Name

Description

Unit

Variable = {Possible Values}

Name

Description

Unit

Variable = {Possible Values}

Enable ROCOF

ROCOF element enable/disable

-

Enable_ROCOF_param= {0, 1}

Level 1

Rate-of-change-of-frequency level.

Hz/s

Rf_param= { [-10, 10] }

Time 1

Time delay associated with Level 1.

s

rocofDelay_param= { [0, 600] }



Inputs, Outputs and Signals Available for Monitoring

Inputs

Name

Description

Name

Description

Vabc

A 3-dimension voltage input for three-phase voltages, in the order of Va, Vb and Vc

Reset

The reset signal for the relay. The relay will be reset when this signal becomes 1.

Outputs

Name

Description

Name

Description

81O

The output of over-frequency relay. By default it is 0, if an over-frequency scenario is detected, it becomes 1.

81U

The output of under-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1

81R

The output of rate-of-change-of-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1.

Sensors

Name

Description

Unit

Name

Description

Unit

m

The calculated frequency by the relay/the actuating quantity of the relay.

Hz



Typical Values for Parameters

The parameter section shows the possible values for each parameter. These values would change to fit the situation of the 81 relay model so they cannot be taken as sole values for each parameter.

Name

Description

Unit

Typical value

Name

Description

Unit

Typical value

Frequency

The nominal frequency of the measured voltage signals.
Both 50 and 60 Hz are supported in the model.

Hz

60

Freezing
time

The freezing time of the 81 relay, when t < freezing time,
the 81 relay is not activated.

s

0.2

Enable Overfrequency

Overfrequency element enable/disable

-

Enabled

Level 1

Over-frequency level 1.

Hz

60.5

Level 2

Over-frequency level 2.

Hz

61.0

Level 3

Over-frequency level 3.

Hz

61.5

Level 4

Over-frequency level 4.

Hz

62.0

Level 5

Over-frequency level 5.

Hz

62.5

Time 1

Time delay associated with Level 1.

s

2.0

Time 2

Time delay associated with Level 2.

s

0.5

Time 3

Time delay associated with Level 3.

s

0.4

Time 4

Time delay associated with Level 4.

s

0.3

Time 5

Time delay associated with Level 5.

s

0.2

Enable  Underfrequency

Underfrequency element enable/disable

-

Enabled

Level 1

Under-frequency level 1.

Hz

59.5

Level 1

Under-frequency level 2.

Hz

59.0

Level 1

Under-frequency level 3.

Hz

58.5

Level 1

Under-frequency level 4.

Hz

58.0

Level 1

Under-frequency level 5.

Hz

57.5

Time 1

Time delay associated with Level 1.

s

2.0

Time 1

Time delay associated with Level 2.

s

0.5

Time 1

Time delay associated with Level 3.

s

0.4

Time 1

Time delay associated with Level 4.

s

0.3

Time 1

Time delay associated with Level 5.

s

0.2

Enable ROCOF

ROCOF element enable/disable

-

Enabled

Level 1

Rate-of-change-of-frequency level.

Hz/s

0.3