Switch

On this page:

Parameters

Symbol

Description

Unit

Symbol

Description

Unit

From Bus

The phase name of the first bus

A unique name

To Bus

The phase name of the second bus

ID

Switch name (ID)

Status

Connect/Disconnect status

  • 1 Closed

  • 0 Opened

Note:

  1. When the switch is on (closed) the series resistance between the From Bus and To Bus is 1e-6 pu.

  2. When the switch is off (open) the series resistance between the From and the To Bus is 1e6 pu The shunt admittance connected to the switch is G=1e-6 pu.

  3. When the switch is used to isolate an unenergized portion of the network that has loads, some numerical instability in the voltage of the isolated bus is expected. However, this will not affect the energized portion of the network.

Available I/O pins

No

Pin Description

Pin Type

Value/Unit

Instruction

No

Pin Description

Pin Type

Value/Unit

Instruction

1

Switches and breakers (each phase)

I/O

  • 1 Closed

  • 0 Opened

switchID/status

2

Get current magnitude of a switch

O

A (RMS)

switchID/Imag

3

Get current angle of a switch

O

Degree

switchID/Iang

Example

See the Switch page in phasor08_IEEE13.xlsx file in the example phasor08.