Documentation Home Page ◇ HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
21 - MHO Distance Relay
Summary
This block models a generic MHO phase distance element with 2 protection zones. A permissive overreach transfer trip logic is also implemented. The relay model does not include other advanced functionalities such as polarizing quantities, memory actions,
loss of potential, reactance functions, load encroachment, etc.
Model overview
The distance relay uses the three-phase voltages and the three-phase currents measured at its end of the transmission line. It uses a generic MHO phase distance element and has two protection zones. The relay characteristics are illustrated on the R-X plane in Figure 3 - 1. The dotted line represents the total impedance vector of the transmission line in the forward direction. The two circles represent the protection zones, commonly known as MHO characteristics. Their centres are both located in the impedance line axis and pass through the origin. The diameter of a given circle will be the total line impedance multiplied by the protected zone percentage. In Figure 3 - 1, we have:
Where R1 and X1 are the total positive sequence resistance and reactance of the line.
For the example of Figure 3 - 1, zone 1 MHO circle has an 80% reach thus the diameter of the zone 1 circle equals to 80% of the total line impedance. In the example, zone 2 MHO circle has a 120% reach.
The model uses Discrete Fourier Transform to calculate the fundamental phasor (magnitude and angle) of Va, Vb, Vc, Ia, Ib and Ic. The zero sequence current phasor is calculated as follows, using the three-phase currents:
The phasors are used to compute the 6 impedances: Za, Zb, Zc, Zab, Zbc and Zca. Take phase A as an example, the impedances are calculated as follows:
Where k is the residual compensation factor:
If any of the computed impedances falls in the circle zone and stays inside for the time delay setting of this zone, the trip signal changes from 0 to 1. A permissive overreach transfer tripping (POTT) logic is also implemented in this model. For the local relay, when zone 2 picks up, a permissive tripping signal (SPT) will be sent out to the other relay at the remote end of the line. If the permissive tripping option is enabled on the remote relay, when it receives the permissive tripping signal and detects the fault in its zone 2, it will trip immediately, instead of waiting for the time delay of zone 2. Similarly, if the local relay receives the permissive tripping signal (RPT) from the remote relay, and detects a fault in its zone 2, it will send out the trip command immediately.
Parameters
Figure 3 - 2 shows the parameter panel for the model. The following parameters can be modified:
Line Parameters Tab
Name | Unit | Description | Default value |
---|---|---|---|
Frequency | Hz | The frequency of the measured current signals. Both 50 | 60 |
Line | km | The total length of the line | 200 |
Positive | ohm/km | The positive sequence resistance of the line | 0.011748 |
Zero | ohm/km | The zero sequence resistance of the line | 0.29014 |
Positive | H/km | The positive sequence inductance of the line | 0.00077518 |
Zero | H/km | The zero sequence inductance of the line | 0.0030241 |
Settings Tab
Name | Unit | Description | Default value |
---|---|---|---|
Zone 1 | % | The forward looking distance of the line that is protected | 80 |
Zone 2 | % | The forward looking distance of the line that is protected | 120 |
Zone 1 | s | The time delay setting for Zone 1. A half-cycle delay is | 0.0083 |
Zone 2 | s | The time delay setting for Zone 2. | 0.3333 |
Enable | n/a | To enable the POTT logic. | disabled |
Input and output signals
The module has 4 inputs and 2 outputs.
21 Relay I/O
I/O name | Type (unit) | Description |
---|---|---|
Vabc | Input (V) | A 3-dimension voltage input for three-phase voltages, in |
Iabc | Input (A) | A 3-dimension current input for three-phase currents, in |
RPT | Input (binary) | Received permissive tripping signal from the remote relay. |
Reset | Input (binary) | The reset signal for the relay. The relay will be reset when |
Trip | Output (binary) | The trip command. By default, it is 0. it will become 1 if a |
SPT | Output (binary) | The permissive tripping signal sent from the local relay. It |
Available monitoring signals
Other than the input and output signals, the following signals are available in the sensor list:
21 Relay monitoring signals
Name | Unit | Description |
---|---|---|
R_0 | ohm | Ra measured by the relay. |
R_1 | ohm | Rb measured by the relay. |
R_2 | ohm | Rc measured by the relay. |
R_3 | ohm | Rab measured by the relay. |
R_4 | ohm | Rbc measured by the relay. |
R_5 | ohm | Rca measured by the relay. |
X_0 | ohm | Xa measured by the relay |
X_1 | ohm | Xb measured by the relay |
X_2 | ohm | Xc measured by the relay |
X_3 | ohm | Xab measured by the relay. |
X_4 | ohm | Xbc measured by the relay. |
X_5 | ohm | Xca measured by the relay. |
These values can be used to plot the impedance trajectory on the R-X plane. For example, in ScopeView, ‘versus (R_0,X_0)’ can be used to plot Za measured by the relay on the R-X plane. The following figure shows the circles representing zone 1 and zone 2 as well
as the Za trajectory during a phase A-to-ground fault.
Impedance trajectory on R-X plane
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter