ZnO Parameters

In EMTP, ZnO elements can be defined by an arbitrary number of segments. However, in HYPERSIM the ZnO model only considers 30 segments.

Remarks

  • Use a maximum of 30 segments to characterize a ZnO.
  • To simulate a ZnO with very small segments, it is necessary to reduce the simulation time step and to increase the maximum number of iterations per time steps. Otherwise, non-characteristic behaviors can be observed in addition to a higher execution time because of the number of iterations required.

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323