2-Winding 3-Phase Series Saturable Transformer

Description

Series transformers are very similar in design to other 3-phase transformers. However, because of their particular connection (series), they are mainly used for series devices such as DVR, active filters, UPFC, etc. The 2-winding series saturable transformer adds modelling of saturation and hysteresis to the linear transformer at the expense of some computation time.

Table of Contents

Mask and Parameters

General Parameters

DescriptionUse this field to add all kinds of information about the component
Flux current modelModel saturation only or saturation with hysteresis
Iteration in saturation modelEnable or disable iteration to achieve more accurate results at the expense of computation time when the saturation segment changes
Base primary/secondary winding voltage (rmsLL)

Base value for PU conversion (kV)

Voltage expressed in kV rms LL

This base voltage and nominal voltage will change, if the corresponding winding connection switches between delta and Y.

Base power (total)Base value for PU conversion (MVA)
Base frequencyBase value for PU conversion (Hz)

Magnetization Impedance Parameters

  • Rm: Equivalent resistance of iron losses of the magnetic circuit (Ω)

Winding Parameters

Secondary connection

Winding type

  • Y ground: Grounded Y connection (can use the internal neutral impedance specified in the other tab)
  • Y floating: Floating Y connection
  • Y neutral: Y connection with impedance connected at the input pin N1 or N2
  • Delta lead: Delta connection with lead of 30°
  • Delta ground: Grounded delta connection (Phase C is grounded)
  • Delta lag: Delta connection with lag of 30°
Voltage (rmsLL)

Rated voltage of the winding (kV)

Y connections: Voltage expressed in kV rms LL

Delta connections: Voltage expressed in kV rms LL

R1, R2Leakage resistance of the winding (Ω)
L1, L2Leakage inductance of the winding (H)


Neutral Impedance Parameters

R2Neutral resistance of the secondary winding; only applies to Y ground (Ω)
L2Neutral inductance of the secondary winding; only applies to Y ground (H)
C2Neutral capacitance of the secondary winding; only applies to Y ground (F)


Saturation Parameters

The saturation is characteristic of the core, thus of the winding and not the type of 3-phase connection (Y, Delta or Zigzag). It is represented only for the magnetization branch (schematically using line segments).

Number of data points

Number of segments of the current-flux saturation curve; only the positive part of the curve must be specified, the negative part being completed by symmetry

Saturation current:Current for each segment of the saturation curve; the origin (0,0) is implied (A)
Saturation fluxFlux for each segment of the saturation curve; the origin (0.0,0.0) is implied (V.s)


Hysteresis Parameters

The main hysteresis cycle is characterized by four parameters. It is measured in DC so as not to include the Foucault losses, which are considered by the parallel resistance (Rm). The initial trajectory is characterized by only one parameter, the initial flux. Two other special parameters serve to minimize the generation of internal nested loops, and their corresponding trajectories, saved in memory (e.g. the loops that are too small will be ignored and their trajectories modelized by a straight line segment).

This is useful since their number must be limited (100 which suffices in most simulated cases). Above this cycle (limited to ±Is), the saturation zone is entered. The saturation is then characterized either by a series of points on the curve or by an inductance that the curve approaches asymptotically. In this last case, the model generates automatically segments (in the positive and negative saturation zone) of equal length (Is).

Saturation data type:Determines if the saturation curve is calculated by the model or defined by a series of segments (Equation, Curve)
Air core inductanceValue of the saturation inductance that the curve approaches asymptotically (H)
Slope at lcFlux slope at coercive current (H)
Coercitive current - IcPositive coercive current at null flux (A)
Saturation current - IsCurrent value of the first point in the saturation zone (A)
Current toleranceSpecial parameter limiting the generation of minor nested loops. When the magnetizing current values at the last inversion point and the preceding inversion point are closer than the specified tolerance (in % of Ic), it is assumed that there is a displacement on a trajectory represented by a straight line segment.
Remanent flux - ΦrPositive remanent flux at null current (V.s)
Saturation flux - ΦsFlux value of the first point in the saturation zone (V.s)
Flux toleranceSpecial parameter limiting the generation of minor nested loops. When the flux values at the last inversion point and the preceding inversion point are closer than the specified tolerance (in % of Φs), it is assumed that there is a displacement on the current loop.
Initial flux (peak)Initial flux determining initial trajectory which is calculated by supposing that it has an inversion point on the main cycle (V.s)
Number of pointsNumber of segments of the current-flux saturation curve; only the positive part of the curve must be specified, the negative part being completed by symmetry
Saturation currentCurrent for each segment of the saturation curve; the first value must be equal to Is (A)
Saturation flux Flux for each segment of the saturation curve; the first value must be equal to Φs (V.s)


Ports, Inputs, Outputs and Signals Available for Monitoring

Ports

Net_1+Positive primary winding connection (supports only 1-phase connections)
Net_1-Negative primary winding connection (supports only 1-phase connections)

Net_2

Secondary winding connection (supports only 3-phase connections)

Net_N2Neutral connection for secondary winding (supports only 1-phase connections)

Inputs

  • None

Outputs

  • None

Sensors

FLUX(a,b,c)Magnetization flux for each phase (V.s)
ILMAG(a,b,c)Magnetization current for each phase (A)
IPRIM(a,b,c)Primary current for each phase (A)
ISEC2(a,b,c)Secondary current for each phase (A)
SEG(a,b,c):

Segment number of the saturation curve

In the saturation model, the numbering is always positive starting at 1 for the last segment in the negative saturation zone.

In the hysteresis model, the numbering is positive/negative starting at 1/-1 in the positive/negative saturation zone. In the hysteresis zone, it takes a null value.