DC2A

Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

DC2A


 

Description

 

This module is based on the IEEE Std 412.5 type DC2A excitation system model [1]. The excitation system uses a field controlled DC commutator to the terminal voltage.

Mask and Parameters

AVR Parameters

image-20260327-201229.png


Expanding the "DC2A diagram" displays the block diagram in the parameters window.

DC2A AVR Block diagram

 

Name

Description

Unit

Name

Description

Unit

Tr

Regulator input filter time constant

s

Tb

Voltage regulator time constant

s

Tc

Voltage regulator time constant

s

Ka

Voltage regulator gain

-

Ta

Regulator time constant

s

Kf

Excitation control system stabilizer gain

-

Tf

Excitation control system stabilizer time constant

s

VRmax

Maximum voltage regulator output

pu

VRmin

Minimum voltage regulator output

pu

 

Exciter Parameters

image-20260327-201244.png

 

Expanding the "Exciter diagram" displays the block diagram in the parameters window.

image-20260327-201640.png

Name

Description

Unit

Name

Description

Unit

Te

Exciter time constant

s

Ke

Exciter constant related to self-excited field

-

Se1, Se2

Exciter saturation factor at the corresponding Vex

pu

Efd1, Efd2

Exciter voltage for the exciter saturation function

pu

Initial Values Mask Parameters

image-20260327-201405.png

Name

Description

Unit

Name

Description

Unit

Efd0

Exciter output voltage initial value

 

pu

The parameter Efd0 can be set manually, by entering a numerical value. It can also be set automatically based on load flow calculations, by entering a referenced synchronous machine variable. For instance, if the name of the synchronous machine on which the excitation system is connected is “SM1”, then Efd0 shall be set as “=SM1.EfdInit” if a thermal machine or a hydraulic machine is used, and as "=SM1.EFD_Init" if a pu standard or pu fundamental machine is used.

The HYPERSIM® simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.

 

Inputs and Outputs and Signals Available for Monitoring

Inputs

Name

Description

Unit

Name

Description

Unit

Vc1

Signal proportional to compensated terminal voltage

If a load compensator block is not used upstream from the exciter block, then Vc1 is equal to Vt (main alternator terminal voltage)

pu

Vref

Voltrage regulator reference voltage

pu

Vs

Is defined as the output voltage of a power system stabilizer (PSS)

pu

Vuel

Underexcitation limiter output

pu

 

Outputs

Name

Description

Unit

Name

Description

Unit

 Efd 

Exciter output voltage

pu

References