Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Frequency Dependent, 6-ph

Description

The FD line model is used to represent transmission lines with frequency-dependent distributed parameters. The equivalent circuit is shown below.

The details regarding the model implementation can be found in:

J. R. Marti, "Accurate modelling of frequency-dependent transmission lines in electromagnetic transient simulations," IEEE Trans. Power App. Syst., vol. PAS-101, pp. 147-55, 01/1982.

Table of Contents


Mask and Parameters

The calculation of the electrical parameters of a line from its geometrical parameters can be done with the Line Data auxiliary module. 

The resulting EMTP output file (*.pun) contains the electrical line parameters required by HYPERSIM.

The user may choose to manually complete the data form, however, it is preferable to provide the parameters of an FD line by loading the pun file in its data form.

General Parameters

NameDescriptionUnitVariable = {Possible Values}
DescriptionUse this field to add information about the component
Description = {'string'}
EMTP (.pun) file for line parametersThe location (path) of the EMTP file (pun file) containing the line parameters
File = {'path.name'}
Transformation matrixTransformation matrix (6 x 6)

Ti = { [-1e64, 1e64] }

Line LengthThe length of the linekm

length = {0, 1e64}

Number of poles for the weighting functionNumber of poles for each phase (mode) of the propagation function

nA = { [0, 1, ..., 39, 40] }

Number of poles for the impedance functionNumber of poles for each phase (mode) of the characteristic impedance function

nZ = { [0, 1, ..., 39, 40] }

First coefficient for characteristic impedanceFirst coefficient for each phase (mode) of the characteristic impedance, i.e., the resistance value for infinite frequencyΩ

Ro = { [-1e64, 1e64] }

Propagation delayPropagation delay for each phases

To = { [-1e64, 1e64] }


Impedance Parameters

NameDescriptionUnitVariable = {Possible Values}
Impedance function coefficientsResidues of the impedance function for each phase

KZ = { [-1e64, 1e64] }

Impedance function polesPoles of the impedance function for each phase

PZ = { [-1e64, 1e64] }


Weighting Parameters

NameDescriptionUnitVariable = {Possible Values}
Weighting function coefficientsResidues of the weighting (propagation) function for each phase

KA = { [-1e64, 1e64] }

Weighting function polesPoles of the weighting (propagation) function for each phase

PA = { [-1e64, 1e64] }

Ports, Inputs, Outputs and Signals Available for Monitoring

Ports

This component supports a 6-phase transmission line 

NameDescription
net_1_1Network connection of phase 1 left (+) side
net_1_2Network connection of phase 1 right side
net_2_1Network connection of phase 2 left (+) side
net_2_2Network connection of phase 2 right side
net_3_1Network connection of phase 3 left (+) side
net_3_2Network connection of phase 3 right side
net_4_1Network connection of phase 4 left (+) side
net_4_2Network connection of phase 4 right side
net_5_1Network connection of phase 5 left (+) side
net_5_2Network connection of phase 5 right side
net_6_1Network connection of phase 6 left (+) side
net_6_2Network connection of phase 6 right side

Inputs

None

Outputs

None

Sensors

At acquisition, the signals available by the sensors are:

NameDescriptionUnit
V_Node(1,2,3,4,5,6)_(1,2)Bus voltage for each phase (1,2,3,4,5,6)V
I(1,2,3,4,5,6)_Node(1,2,3,4,5,6)_(1,2)Current for each phase (1,2,3,4,5,6)A

The (1,2) in the previous table indicates the name of the bus at each end of the line (1 for left (+) side and 2 for the right side)

The Data of a 6-phase FD Model

The following figure shows the geometrical data of a double circuit transmission line as an example to simulate a 6-phase FD model. 

The calculation of the electrical parameters can be done with the Line Data auxiliary module.

The EMTP-type output file for the calculation of the parameters for the FD line model:

A portion of the pun file generated with the Line Data auxiliary module:



OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter