IEC60044-8 Packing

Block

Mask

Description

This IEC60044-8 packing block receives the data from the VBC/PCP HDLC Serial Communication Interface block and generates the signals needed by the DataOut block.

Note: The VBC/PCP HDLC Serial Communication Interface block implements the IEC60044-8 protocol between a valve balancing controller (VBC) and a pole controller based on HDLC serial protocol. 

Parameters

This block has no parameters.

Inputs

ValidThis port should receive a signal to indicate that data present in the Data input is valid.

Data

This is a 128 bits wide data-block in the received HDLC frame:

Bit PositionData Descriptions

15:0

Block X Data R0

31:16

Block X Data R1

47:32

Block X Data R2

63:48

Block X Data R3

79:64

Block X Data R4

95:80

Block X Data R5

111:96

Block X Data R6

127:112

Block X Data R7

where X represents one of the 16 Blocks of the HDLC frame (see VBC/PCP HDLC Serial Communication Interface for HDLC Frame description).

Outputs

DataOut

This port contains a valid bit and a serialized data of the 128 bits wide data-block in the received HDLC frame. It is to be connected to the DataOuti input port of the DataOut block corresponding to the channel selected for the DataOut signal.
DataSyncThis port represents a pulse indicating the update of the DataOut port. It is to be connected to the DataSynci input port of the DataOut block corresponding to the channel selected for the DataOut signal.

Characteristics and Limitations

This block has no specific characteristics or limitations.